Current location:home page > PRODUCT > ELCB

DZ47LE-63

Release time:2024-09-03popularity:20

Leakage protection circuit breakers are suitable for  use as leakage protection in circuits with AC 50Hz,  rated voltage of 230V/400V, and rated current up to 63A . When someone is electrocuted or the leakage current  of the circuit exceeds the specified value, the  residual current circuit breaker can automatically cut  off the power supply within 0.1 seconds, ensuring  personal safety and preventing accidents caused by  leakage current of the equipment. Leakage circuit  breakers have overload and short circuit protection  functions, which can be used to protect the circuit  from overload and short circuit, and can also be used  for infrequent replacement of the circuit under normal  circumstances. 

This product complies with the GB16917.1 standard.


CategoryI△n
(ma)
In
(A)
Maximum (residual current) breaking time(S)
I△n2I△n5I△n250mA
Indirect Contact>30Any Value0.20.10.04-
Direct Contact≤30Any Value0.10.1-0.04

SortType of separatorRated current
of separatorIn(A)
I/InSeparation time(t)Initial stateExpected resultsAmbient temperature
aB、C、D≤631.13≥1hCold stateUndivided30℃~50℃
b1.45<1hHot stateSeparate
c≤322.551s<t<60sCold stateSeparate
>321s<t<120s
dBAll values3≥0.1sUndivided
C5
D10
eB5<0.1sSeparate
C10
D20

Inm
A
In
A
Width
mm
Number of poles
1P+N2P3P3P+N4P
63≤32L127±0.4227±0.4236±0.545±0.545±0.5
40、50、6336±0.536±0.549.5±0.563±0.663±0.6
≤32Lmax45639099117
40、50、635472104117135